home *** CD-ROM | disk | FTP | other *** search
/ Spec Disk 1998 Spring 4.0 / Spec Disk 1998 Spring 4.0.iso / generic / 11201wfc.gen < prev    next >
Text File  |  1998-06-10  |  6KB  |  155 lines

  1.     SECTION 11201
  2.  
  3.     WASH TROUGHS
  4. NOTE ** Warminster Fiberglass Co. wash troughs.
  5. NOTE ** 
  6. NOTE ** This section is based on products manufactured by Warminster Fiberglass Co., which is located at the following address:
  7. NOTE **      P.O. Box 188
  8. NOTE **      Southampton PA  18966-0188
  9. NOTE **      Tel:  (215) 953-1260
  10. NOTE **      Fax:  (215) 357-7893
  11. NOTE ** 
  12. NOTE ** Warminster Fiberglass Co. has manufacturing facilities in Southampton PA and in Jacksonville TX, and manufactures a wide line of fiberglass reinforced polyester resin products for the water and waste treatment industry, including instrument consoles, Palmer-Bowlus flumes, Parshall flumes, slide gates, wash troughs, effluent troughs, finger weirs, weir plates, scum baffles, metering manholes, density current baffles, and odor control systems.
  13. NOTE ** 
  14. NOTE ** Warminster also manufactures fiberglass doors and frames and buildings, shelters, and enclosures for a wide range of uses.
  15. NOTE ** 
  16. NOTE ** SECTION 11201 - WASH TROUGHS, Copyright 1997, The Architect's Catalog, Inc.
  17. NOTE **  
  18.  
  19. PART 1    GENERAL
  20.  
  21. 1.1    SECTION INCLUDES
  22.  
  23.     A.    Wash troughs.
  24.  
  25. 1.2    RELATED SECTIONS
  26. NOTE ** Delete any sections below not relevant to this project; add others as required.
  27. NOTE **  
  28.     A.    Section 03300 - Cast-In-Place Concrete.
  29.  
  30.     B.    Section 08342 - Fiberglass Doors and Frames.
  31.  
  32.     C.    Section 11202 - Effluent (Collection) Troughs (Launders).
  33.  
  34.     D.    Section 11203 - Finger Weir Pans.
  35.  
  36.     E.    Section 11204 - Weir Plates, Scum Baffles, and Brackets.
  37.  
  38.     F.    Section 11205 - Density Current Baffle System.
  39.  
  40.     G.    Section 11206 - Palmer-Bowlus Flumes.
  41.  
  42.     H.    Section 11207 - Parshall Flumes.
  43.  
  44.     I.    Section 11208 - Metering Manholes.
  45.  
  46.     J.    Section 11286 - Slide Gates and Guides.
  47.  
  48.     K.    Section 11305 - Odor Control System.
  49.  
  50.     L.    Section 13122 - Pre-Engineered Fiberglass Buildings.
  51.  
  52.     M.    Section 13411 - Instrument Consoles.
  53.  
  54. 1.3    REFERENCES
  55. NOTE ** Delete references from the list below that are not actually required by the text of the edited section.
  56. NOTE **  
  57.     A.    ANSI/NSF 61 - Drinking Water System Components - Health Effects; NSF International.
  58.  
  59.     B.    ANSI/AWWA F101 - Contact Molded, Fiberglass-Reinforced Plastic Wash Water Troughs and Launders; American Water Works Association.
  60.  
  61.     C.    ASTM D 638 - Standard Test Method for Tensile Properties of Plastics.
  62.  
  63.     D.    ASTM D 790 - Standard Test Methods for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical Insulating Materials.
  64.  
  65. 1.4    SUBMITTALS
  66.  
  67.     A.    Submit under provisions of Section 01300.
  68.  
  69.     B.    Product Data:  Test results of fiberglass reinforced plastic laminate.
  70.  
  71.     C.    Shop Drawings:  Show:
  72.         1.    Critical dimensions, jointing and connections, fasteners and anchors.
  73.         2.    Materials of construction.
  74.         3.    Sizes, spacing, and locations of structural members, connections, attachments, openings, fasteners, and loads.
  75.  
  76.     D.    Samples:  8-inch square sample of fiberglass reinforced plastic laminate.
  77.  
  78.     E.    Manufacturer's installation instructions.
  79.  
  80. 1.5    DELIVERY, STORAGE, AND HANDLING
  81.  
  82.     A.    Store products indoors and protect from construction traffic and damage.
  83.  
  84. PART 2    PRODUCTS
  85.  
  86. 2.1    MANUFACTURER
  87.  
  88.     A.    Provide products manufactured by Warminster Fiberglass Company; P.O Box 188, Southampton PA 18966-0188; ASD.  Tel. (215) 953-1260, Fax. (215) 357-7893.
  89. NOTE ** Delete one of the two following paragraphs; coordinate with Division 1 requirements.
  90.  
  91.     B.    Requests for substitution will be considered in accordance with provisions of Section 01600.
  92.  
  93.     C.    Substitutions:  Not permitted.
  94.  
  95. 2.2    WASH TROUGHS
  96.  
  97.     A.    Material:  Fiberglass reinforced polyester resin, 1/4 inch thick, average; inside surface of smooth gel coat finish; outside surface resin sealed with no exposed glass fibers; molded-in color with ultraviolet inhibitor.
  98.         1.    Tensile strength (ASTM D 638):  14,000 psi.
  99.         2.    Flexural strength (ASTM D 790):  25,000 psi
  100.         3.    Flexural modulus (ASTM D 790):  1,000,000 psi.
  101.         4.    Color:  White.
  102.  
  103.     B.    Construction:  Comply with requirements of ANSI/AWWA F101 and ANSI/NSF 61; provide NSF labelled products and proof of certification.
  104.         1.    Designed to support applied water loadings at each location.
  105.         2.    Designed to resist deflection under full buoyant and gravity water loads with maximum upward and downward deflection less than or equal to L/1000 where L equals the unsupported trough length; maximum deflection at midpoint not greater than 3/16 inch.
  106.         3.    Round bottom, vertical sides.
  107.         4.    Top edges straight with not more than 1/8 inch deviation from true plane.
  108.         5.    Longitudinal steel stiffening ribs integrally molded on the outside of troughs to ensure rigidity.
  109.         6.    Plastic spacer rods to maintain uniform width over the length of trough.
  110.         7.    2 inch wide, 1/2 inch thick wall, grouting rib molded to outside of each trough at the gullet end to act as a water stop when trough is grouted in place.
  111.         8.    Slotted holes in closed end of trough to allow a minimum vertical level adjustment of 1 inch.
  112.         9.    Stainless steel wall anchors and flat bars.
  113. NOTE ** The following two paragraphs are optional.
  114. NOTE **          10.    Saddle at blind end.
  115.         11.    Straight edge weir plates, factory-installed.
  116.  
  117. PART 3    EXECUTION
  118.  
  119. 3.1    EXAMINATION
  120.  
  121.     A.    Verify that dimensions are correct and project conditions are suitable for installation.  Do not proceed with installation until unsatisfactory conditions have been corrected.
  122.  
  123. 3.2    INSTALLATION
  124.  
  125.     A.    Install products in accordance with manufacturer's instructions.
  126.  
  127.     B.    Ensure that products are installed plumb and true, free of warp or twist, within tolerances specified by the manufacturer and as indicated in the contract documents.
  128.  
  129.     C.    Set in place with weir edges to elevations indicated.
  130.  
  131.     D.    Level weir edges to within 1/8 inch of level over entire length.
  132.  
  133.     E.    Grout in place after leveling.
  134.  
  135. 3.3    ADJUST AND CLEAN
  136.  
  137.     A.    Clean surfaces in accordance with manufacturer's instructions.
  138.  
  139.     B.    Remove trash and debris, and leave the site in a clean condition.
  140.  
  141.     END OF SECTION
  142. ??
  143.  
  144.  
  145.  
  146.  
  147.  
  148.  
  149.  
  150.  
  151.  
  152.     11201-1